VIAVI SmartClass Fiber MPOLx MPO optical loss test set units
SmartClass Fiber MPOLx

SmartClass Fiber MPOLx MPO Optical Loss Test Sets for Tier 1 (Basic) Certification

MPO optical loss test set that measures length, loss and polarity on all 12 fibers and inspects MPO end faces for Tier 1 certification.

Optical Interface
MPO-12 Interface pinned. Compatible with 50/125 μm/PC Multimode MPO-12, 9/125 μm/APC Singlemode MPO-12. MTP Adapter with Shutter
Detector Type
InGaAs
Wavelength Range
850 to 1550 nm
Wavelength Settings
850 nm, 1300 nm, 1310 nm, 1550 nm
Datasheet

Overview

The VIAVI SmartClass Fiber MPOLx is a dedicated optical loss test set for performing the test requirements of Tier 1 (Basic) certification on links with native MPO connectivity. It combines a light source and a power meter so that MPO length, optical loss and polarity can be measured, fiber end faces inspected and certification reports generated with a single solution.

The set consists of identical local and remote units, giving the technician visibility and control from both the light source and the power meter. Each unit has a 3.5" color touch screen and integrated inspection for both bulkhead and trunk connectors, so a single technician can inspect MPO end faces and run tests from either end of the connection.

Test results for all 12 fibers of the connector are delivered in less than 6 seconds. Results are color coded pass/fail and include the test limit, fiber length, test wavelengths, loss values, margins and polarity for each fiber.

Software and reporting

The MPOLx integrates with FiberChekPRO and is supported by SmartClass Fiber Software, J-Reporter and ReportPRO for results management and certification reporting.

Key Features

  • Measures MPO length
  • Measures optical loss at multiple wavelengths
  • Checks polarity for all 12 MPO fibers
  • Native MPO testing directly on the devices
  • Test results for all 12 MPO fibers in <6 seconds
  • Native MPO end-face inspection and automated analysis for trunk cables and bulkheads
  • Dual wavelength optical light sources
  • Encircled flux compliant
  • 3.5" color touch screen on all MPOLx devices
  • Generates certification reports
  • All-day battery life
  • Identical local and remote units with control from both ends
  • Integrates with FiberChekPRO

Specifications

Power Meter
Optical Interface MPO-12 Interface pinned. Compatible with 50/125 μm/PC Multimode MPO-12, 9/125 μm/APC Singlemode MPO-12. MTP Adapter with Shutter
Detector Type InGaAs
Wavelength Range 850 to 1550 nm
Wavelength Settings 850 nm, 1300 nm, 1310 nm, 1550 nm
Calibrated Wavelengths (Multimode) 850 nm, 1300 nm
Calibrated Wavelengths (Singlemode) 1310 nm, 1550 nm
Power Measurement Range -50 to +3 dBm
Max. Permitted Input Level +3 dBm
Overall Measurement Uncertainty (Multimode) ± 0.7 dB ± 1 nW
Under reference conditions at calibrated wavelengths, -5 to +45°C
Overall Measurement Uncertainty (Singlemode) ± 0.6 dB ± 1 nW
Under reference conditions at calibrated wavelengths, -5 to +45°C
Linearity ±0.15 dB
Measurement Units dB, dBm
Display Resolution 0.01 dB
Power Meter Functions Absolute, relative, pass/fail
Warm-Up Time 20 minutes
Light Source
Optical Interface (Multimode) MPO-12 Interface pinned, 50/125 μm/PC Multimode. MTP Adapter with Shutter
Optical Interface (Single-Mode) MPO-12 Interface pinned, 9/125 μm/APC Singlemode. MTP Adapter with Shutter
Source Type and Wavelengths (Multimode) LED source, 850 nm ± 20 nm, 1300 nm ± 20 nm
Source Type and Wavelengths (Single-Mode) Fabry-Perot laser diode, 1310 nm ± 20 nm, 1550 nm ± 20 nm
Spectral Width (FWHM) (Multimode) <170 nm
Spectral Width (FWHM) (Single-Mode) <5 nm
Launch Condition (Multimode) Encircled Flux compliant to TIA-526-14B and IEC 61280-4-1
At the output of the EF-TRC. Variations between EF measurement equipment may occur but EF compliance can be expected with a 95% confidence factor. Valid for IEC 61280-4-1 at 850 nm.
Output Power (Multimode) -26 dBm
Typical output
Output Power (Single-Mode) -6 dBm
Typical output
Stability 15 min/8 hr ±0.05 / 0.25 dB
Single Channel, +5 to +45°C with ΔT = ±0.3 K after a 20-minute warm-up
Source Mode CW
Loss/Length Application
Testing Speed for 12 Channels < 10 seconds (typ. 6 seconds)
Excludes referencing and connection times
Pass/Fail Limit Standards (Multimode) Link validation, TIA-568.3-E, ISO 14763-3, 40 GBASE SR4, 100 GBASE SR4, 100 GBASE SR10
Pass/Fail Limit Standards (Single-Mode) Link validation, TIA-568.3-E, ISO 14763-3
Fiber Types (Multimode) 50/125 μm
Fiber Types (Single-Mode) 9/125 µm
Nominal Test Wavelengths (Multimode) 850/1300 nm
Nominal Test Wavelengths (Single-Mode) 1310/1550 nm
Maximum Length Measurement (Multimode) 1 km
Maximum Length Measurement (Single-Mode) 10 km
Length Measurement Accuracy ±1.5 m ±1% of length
Loss Measurement Uncertainty ±0.15 dB
Excludes fiber connector uncertainties. After 20 min warm up, at constant temperature, no charging. Multimode with 50/125 µm fibers (NA = 0.20); single-mode with 9/125 µm fibers (NA = 0.10)
Patchcord Microscope (PCM)
Interface
2330/11S, 2330/01S, 2330/31
FMAX adapters
PCM models include 2330/11S, 2330/01S and 2330/31
Auto Pass/Fail Analysis Standards
2330/11S, 2330/01S, 2330/31
IEC 61300-3-35 and custom limits
Live Image
2330/11S, 2330/01S, 2330/31
320 x 240 x 8 bit grey, 10 fps
Light Source
2330/11S, 2330/01S, 2330/31
Blue LED, 100.000+ hours life
Lighting Technique
2330/11S, 2330/01S, 2330/31
Coaxial
Magnification Field-of-View Low/High
2330/11S, 2330/01S, 2330/31
Horizontal: 740/370 µm; Vertical: 550/275 µm
External Probe External USB connected P5000i digital inspection probe supported
General
Display High-contrast 3.5” color LCD with touch-screen functionality
Data Memory Up to 10.000 loss test results (>1000 including inspection)
Data Readout Via client USB interface, and wireless via USB WiFi/Bluetooth dongle
Electrical Interfaces 2 x USB host, 1x micro USB, Ethernet
Power Supply 12 V, 2A with interchangeable wall plug for EU, UK, US, and AU
Battery Li-ion pack 3.7 V, 20 Wh (optional 8 NiMH/dry batteries)
Battery Life (Li-ion battery pack) >12 hr
Recommended Recal. Interval 3 years
Dimensions (H x W x D), without PCM 208 x 112 x 64 mm (8.2 x 4.4 x 2.5 in)
Dimensions (H x W x D), with PCM
2330/11S, 2330/01S, 2330/31
208 x 153 x 64 mm (8.2 x 6.0 x 2.5 in)
Weight, without PCM 600 g (1.6 lb)
Includes rechargeable battery
Weight, with PCM
2330/11S, 2330/01S, 2330/31
750 g (1.85 lb)
Includes rechargeable battery
Operating Temperature Range –5˚ to +45˚C (23˚ to 113˚F)
Storage Temperature Range –25˚ to +55˚C (–13° to 131°F)

Specifications are taken from the manufacturer's documentation. See the datasheet for complete and current values.

Applications

  • Tier 1 (Basic) fiber certification
  • MPO/MTP trunk and link testing
  • Data center fiber networks
  • Enterprise fiber cabling certification
  • Parallel optics link validation
  • MPO end-face inspection

Documents & Resources

SmartClass Fiber MPOLx MPO Optical Loss Test Sets
datasheet · PDF
Quick Card: SmartClass Fiber MPOLx - Testing MPO/MTP Terminated 12 Strand Fiber
manual · PDF
SmartClass Fiber MPOLx
brochure · PDF
SmartClass Fiber MPOLx Overview
other
How-To Videos: SmartClass Fiber MPOLx
other
SmartClass Fiber Software
software
Testing MPO Networks: Best Practices & Tools for Fiber Certification
app note · PDF
Essentials of Multi-Fiber MPO Testing Series - Episode 1: Overview of MPO Connectors
other
Essentials of Multi-Fiber MPO Testing Series - Episode 2: Dealing with Contamination on MPO Connector
other
Essentials of Multi-Fiber MPO Testing Series - Episode 3: Understanding MPO Connector Polarity
other
Essentials of Multi-Fiber MPO Testing Series - Episode 5: MPO Connectivity
other
MPO and Dense Fiber Networks Solutions from VIAVI
other
MPOLx - Inspecting MPO Connectors With The Patch Cord Microscope
other
MPO Challenges Dealing with Multi-fiber Connectors and Cables
other
Reference Guide to Fiber Optic Testing: Volume 1
app note
Reference Guide to Fiber Optic Testing: Volume 2
app note
Twice the Productivity with VIAVI Solutions: Field Technicians get full control on both Local and Remote ends of test solutions
app note · PDF
Data Center Use Case Test Guide
app note · PDF
Quick Tech Tip: Inspecting MPO Cables is Critical
manual · PDF
Fiber Inspection Tips and Adapters
brochure · PDF
Test and Maintenance Solutions for Enterprise and Data Center Operators
brochure · PDF
MPOLx Panduit Approval
other · PDF
MPOLx - Device Overview
other
MPOLx: Setting a Reference for Unpinned Systems (Adapter Cord Method)
other
MPOLx: Setting a Reference for Unpinned Systems (Gender Neutral Method)
other
Winning with MPO Testing
app note · PDF
J-Reporter Software
software
ReportPRO Software
software
VIAVI Care Support Plans
other · PDF
Inspect Before You Connect Video Series
other
Cleaning and Testing Parallel Optics
app note · PDF
Testing Parallel Optics
app note